Specifications
CONDITIONS
VOLTAGE DC
(VDC)
CURRENT
(Amp)
POWER
(W)
OPERATING
TEMPERTURE
CABLE LENGTH
UL
REFERENCE
NUMBER
Input
DC Input (NSC)
+12 VDC 0.04 Amp 0.48
32° - 122°F
(0° - 50° C)
Lock Control Circuit
100 ft (30 m) = 22 AWG ● 0.65mm ● 0.33mm2
200 ft (60 m) = 18 AWG ● 1.02mm ● 0.82mm2
Hi-O CAN Bus Total Length 100 ft (30 m) -
22 AWG ● 0.65mm ● 0.33mm2
Maximum between drops 30 ft (10 m)
22 AWG ● 0.65mm ● 0.33mm2
ELMAxNN
X = K for Black
G for Gray
+24 VDC 0.04 Amp 0.96
DC Input (MAX)
+12 VDC 1.2 Amp 14.4
+24 VDC 1.2 Amp 28.8
Output
DC Output
(MAX)
AUX 12 VDC
Input @
Controller
Unregulated Jumpers +10 to +12 VDC 0.46 Amp* 5.52
AUX 24 VDC
Input @
Controller
Unregulated Jumpers +23 to +24 VDC 1.0 Amp* 24.0
Regulated Jumpers – 12 VDC +10 to +12 VDC 1.0 Amp* 12.0
PoE Input @
Controller
Unregulated Jumpers +16.5 to 24 VDC 0.30 Amp* 7.2
Regulated Jumpers – 12 VDC +10 to +12 VDC 0.60 Amp* 7.2
Output Power Selection
P103
1 & 2 2 & 3
12 VDC CAN / DC Input
Mounting
EDGE EVO
®
Lock ModuLe
ELM
InstallatIon GuIde
82301-901, Rev C.1
December 2012
© 2009 - 2012 HID Global Corporation. All rights reserved.
15370 Barranca Parkway
Irvine, CA 92618-2215
USA
NSC = Normal Standby Condition
* Combined output rating not to exceed V*I = W
1.2 Amp (+24 VDC AUX Input, 28.8 W)
1.2 Amp (+12 VDC AUX Input, 12.96 W)
CAUTION: Some magnetic locks exhibit both high inrush current when activated and a high instantaneous
break voltage when de-energized due to magnetic eld collapse. It is recommended you use of a snubber circuit
across the controlling relay terminals to protect the controlling relay contacts. Go to support.hidglobal.com, see
Solution 891 - How do I wire a High In-Rush Current locking device to VertX/EDGE EVO. Not evaluated by UL.
This Hi-O interface module is wired to interface the EDGE EVO device
(Controller/Reader & Module or Networked) with electronic door components.
The Lock module provides outputs to an electronic locking device.
Install the EDGE EVO Lock Module within
a UL Listed single-gang electrical box or
optionally within a hollow metal door frame
(shown).
Vue de la page 0
1 2

Résumé du contenu

Page 1 - EDGE EVO

SpecificationsCONDITIONSVOLTAGE DC (VDC)CURRENT (Amp)POWER (W)OPERATING TEMPERTURECABLE LENGTHUL REFERENCE NUMBERInputDC Input (NSC)+12 VDC 0.04 Amp 0.

Page 2 - Regulatory

RegulatoryULConnect only to a Listed Access Control / Burglary power-limited power supply, or Listed Access Control / Burglary PoE (Power-over-Etherne